95/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
6 Fuel-air ratio control (FARC)
22.05.2018
Tolerance
Actuator / variable speed drive
Display on the
AZL52
0.3°/0.5%
0.4°/0.5%
0.5°/0.5%
0.6°/0.6%
●
●
●
1.2°/1.2%
Figure 43: Display on AZL52
Β
Note!
The parameter influences the tolerance of the position assessment for
all
actuators
(actuators and variable speed drive) at the same time.
Attention!
This parameter may only be set in a way that does not affect the combustion.
It may be necessary to set a higher residual oxygen content on the system or to
install an O2 supervision if this value is increased above the value set in the
delivery state.