20 Flue gas recirculation (FGR) function (LMV50/LMV51.3/LMV52)
22.05.2018
Β
Note!
The full scope of setting
TCautoDeact
is possible only when the flue gas temperature
is acquired via the load controller input (X60…).
When the temperature is acquired via the PLL52 input (X86…) and the O2 trim
controller / alarm is active (not
CtrlAutoDeac
), flue gas recirculation (FGR) mode
temperature-compensated
cannot be used (would lead to error
C:F6 D:2
).
When operating mode
O2 Control
is deactivated (
man deact
), operating mode
TCautoDeact
can be used if the flue gas temperature is acquired via PLL52 (X86…).
Β
Note!
Setting
deactMinpos
is recommended when commissioning the plant, since
erroneous
temperature values
will not be stored.
Parameter
FGR-Mode (deactivated / time / temperature / temp.contr. /
TCautoDeact / Aux3 Minpos / auto deact)