276/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
19 O2 trim control with LMV52 and PLL52
22.05.2018
Terminal
marking
Connection
symbol
S
af
et
y
cl
as
s
In
p
ut
O
ut
p
ut
Description of connection
Electrical rating
O2 module
X81
PIN 6
III
˜
Temperature compensation QGO20 (U3)
DC [0...2 V], Ri > 100 k
ς
PIN 5
˜
Power supply temperature compensation
(G2)
DC [12...18 V], Ra = 20
ς
PIN 4
˜
˜
GND (M)
PIN 3
˜
Thermocouple (B2)
DC [0...33 mV], Ri > 100 k
ς
PIN 2
˜
˜
GND (M)
PIN 1
˜
Nernst voltage (B1)
DC [-25...1 mV], Ri > 100 k
ς
X84
PIN
5 GND
III
˜
Signal reference
PIN
4 CANL
˜
Communication signal
DC U <= 5 V, Rw = 120
ς
,
level to ISO-DIS 11898
PIN
3 CANH
˜
Communication signal
PIN
2 12VAC2
˜
AC supply for O
2
module
AC 12 V +10% / -15%, 0...60 Hz,
fuse max. 4 A
PIN
1 12VAC1
˜
AC supply for O
2
module
X85
PIN
5 GND
III
˜
Signal reference
PIN
4 CANL
˜
Communication signal
DC U <= 5 V, Rw = 120
ς
,
level to ISO-DIS 11898
PIN
3 CANH
˜
Communication signal
PIN
2 12VAC2
˜
AC supply for O
2
module
AC 12 V +10% / -15%, 0...60 Hz,
fuse max. 4 A
PIN
1 12VAC1
˜
*
AC supply for O
2
module
Combustion air / flue gas temperature sens
or
X86
PIN 3
III
˜
Shield connection
PIN 2
˜
Signal reference
PIN 1
˜
Flue gas temperature sensor input
Pt1000 / LG-Ni 1000
X87
PIN 3
III
˜
Shield connection
PIN 2
˜
Signal reference
PIN 1
˜
Combustion air temperature input
Pt1000 / LG-Ni 1000
X89-02
PIN
1 PE
I
˜
Protective earth (PE)
PIN 2 Q5 N
˜
QGO20
heating
PIN 3 Q4 L
˜
QGO20 heating
At AC 120 V +10 % / -15%,
50...60 Hz, Imax. 2.5 A
At AC 230 V +10 % / -15%,
50...60 Hz, Imax. 2.5 A
X89-01
PIN
1 PE
I
˜
Protective earth (PE)
PIN
2 N
˜
Power supply neutral conductors (N)
PIN
3 L
˜
Power supply live conductor (L)
AC 230 V +10 %/ -15%,