4 Burner control
22.05.2018
4.2.3.2 Repetition counter
With heavy oil
Repetition counter value: Heavy oil direct start
Β
Note:
Changes only become active after a reset (power on / reset)
With start release
Repetition limit value: Start prevention
Β
Note:
Changes only become active after a reset (power on / reset)
With safety loop
Repetition limit value: Safety loop
Β
Note:
Changes only become active after a reset (power on / reset)
Only LMV50:
With no flame at the
end of safety time
Repetition limited value: No flame at the end of first safety time
Setting choices for gas and oil together:
1…3
⇓
none…2 repetitions
Β
Note!
Changes only become active after a reset (power on / reset)
Caution!
Setting only in accordance with the relevant application
standard.
With loss of flame
Repetition limit value: Loss of flame
Β
Note!
Changes only become active after a reset (power on / reset).
Caution!
Setting only in accordance with the relevant application
standard.
Number of repetitions = setting value - 1.
That is:
∂
Value = 1: No repetition
∂
Value = 2: Equals
1
repetition
Caution!
Value 16 represents an unlimited number of repetitions!