70/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
4 Burner control
22.05.2018
4.2.3.14 Startup sequence stop in phase 36
The burner's startup sequence can be stopped in phase 36 via input X5-03 pin 3 if
parameter
Config X5-03
has been set to
DeaO2/Stp36
.
The stop takes place if
no
mains voltage is present.
Attention!
This function may only be used for
non-safety-related
multiple burner
applications.
Ι
Note!
At the same time as this parameter setting, input X5-03 pin 2 is set
to deactivation of
O2 trim control
(
DeaO2/Stp36)
.
This function cannot be used if the inputs (X5-03 pin 2 / pin 3) are being used to
connect an external load controller
(LC_OptgMode = ExtLC X5-03)
↑
invalid parameter setting.
Parameter Config X5-03 (DeaO2/Stp36)
4.2.3.15 Cooling function in standby mode (only LMV50)
In order to cool the burner in standby mode, a cooling function can be activated using
parameters.
The cooling function is started with a mains voltage signal at input X5-03 pin 3:
∂
The fan is switched on and supervised in the same way as for
continuous purging
∂
The actuators used for determining the amount of air are driven to their postpurge
positions
∂
If no mains voltage signal is present, the device behaves as for
without continuous
purging
in standby mode
Parameter Config X5-03 (CoolFctStby)
Attention!
This function may only be used for
non-safety-related
multiple burner applications.
This means, for example, that the function may not be used for safety-related
purging in plants with several burners in one combustion chamber.
Β
Note!
∂
This function cannot be used if the inputs (X5-03 pin 2 / pin 3) are being used to
connect an external load controller (LC_OptgMode = ExtLC X5-03)
↑
invalid
parameter setting
∂
When using the cooling function, the
ContinuousPurge
parameter must not be set
to
off Sloop
or
deac/VSD-SL
as these settings cancel each other out, potentially
resulting in error messages
4.2.3.16 Long postpurge time (only LMV50 / LMV52.4)
If a long postpurge time is required, an additional time can be set in one-minute
intervals via an additional,
non
fuel-specific parameter
PostpurgeT3long.
This time is added to the two fuel-specific times
PostpurgeT3Gas / Oil
.
Parameter PostpurgeT3long