207/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
12 Description of connection terminals (AC 230 V)
22.05.2018
Description of connection terminals (cont’d)
T
er
m
in
a
l
m
ar
ki
n
gs
Connection symbol
S
af
et
y
cl
as
s
In
p
ut
O
ut
p
ut
Description of connections
Electrical rating
X5-01
PIN 1
I
˜
Protective earth (PE)
PIN 2
˜
Pressure switch min-oil (Pmin-oil)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN 3
˜
Power signal for pressure switch-
min-oil (Pmin-oil)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
X5-02
PIN 1
I
˜
Protective earth (PE)
PIN 2
˜
Pressure switch-max-oil (Pmax-oil)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN 3
˜
Power signal for pressure switch-
max-oil (Pmax-oil)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
X5-03
PIN 1
I
˜
Controller (ON / OFF)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN 2
˜
Controller closes / stage 3
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN 3
˜
Controller opens / stage 2
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN 4
˜
Power signal for control of controller
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
X6-01
PIN 1
I
˜
Start release oil (START)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN 2
˜
Power signal start release oil
(START)
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
PIN 3
˜
Direct heavy oil start
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
PIN 4
˜
Power signal direct heavy oil start
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
X6-02
PIN 1
I
˜
Protective earth (PE)
PIN 2
˜
Neutral conductor (N)
PIN 3
˜
Oil pump / magnetic coupling
AC 230 V +10 % / -15 %, 50...60 Hz,
2 A, cos
ι
0.4
X6-03
PIN 1
I
˜
Protective earth (PE)
PIN 2
˜
Neutral conductor (N)
PIN 3
Fuel valve (shut-off valve-oil)
AC 230 V +10 % / -15 %, 50...60 Hz,
1 A, cos
ι
0.4