Basic Documentation LMV5...
CC1P7550en
7 Boiler controller / load controller
22.05.2018
If the internal
temperature limiter
function is used, the time constant «T» of the
temperature sensor with protection pocket must not exceed 45 seconds.
7550d19E/0502
1
T
Ι
0.63
T
em
p
er
a
tu
re
Ι
M
X
a
Time t
Figure 60: Instant temperature change of test medium to determine the time constant
Legend
Ι
M
Temperature of test medium
Xa
Output signal of temperature sensor
T
Time constant
Requirements placed on
sensor and protection
pocket