Basic Documentation LMV5...
CC1P7550en
7 Boiler controller / load controller
22.05.2018
BACS for control via bus with the internal load controller.
The internal load controller is connected via the AZL5 and an external bus interface
(Modbus) with a BACS. The BACS transmits «only» predefined setpoints to the internal
controller. This means that the actual control is provided by the internal load controller.
Terminals X62 pin 1 and X62 pin 2 can be used for changeover from the external
predefined setpoint to the internal setpoint W1 (e.g. in the event the BACS fails),
triggered via a potential-free contact (load controller software version V01.50 or higher).
AZL5...
CAN module
(basic unit)
FARC (BU)
Demand
for heat
BC (BU)
Manipulated variable,
demand for heat
Manipulated variable,
demand for heat
CAN bus
75
5
0
b
03
e
/0
7
04
Setpoint
Setpoint
Manipulated
variable
0...100 %
Internal
load controller
Setpoint
Modbus /
e-bus
BMS
Ja
ck
X
72
X62.1
X62.2
Figure 49: Operating mode 3 with load controller
Operating mode 3
(int LC bus)