9 Commissioning instructions for the LMV5
22.05.2018
The burner control proceeds with the startup sequence until the ignition position (phase
36) is reached. There, the burner control stops again for setting the ignition positions of
the actuators.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
RatioControl
OilSettings
SpecialPositions
IgnitionPos
IgnitionPosOil
IgnitionPosAir
IgnitionPosAux1
IgnitionPosAux2
Only LMV52
IgnitionPosAux3
IgnitionPosVSD
LMV50/LMV51.3/
LMV52
To repeatedly verify the ignition positions, the control sequence can be stopped in
interval phase 44 or 52 (interval with ignited flame on completion of the respective
safety time).
When the program stop is deactivated, the burner proceeds with its program until normal
operation is reached (phase 60).
If the switching points of the burner stages have not yet been defined, the ignition
positions of the actuators are used as the first stage for the moment.
24. Ignition positions