9 Commissioning instructions for the LMV5
22.05.2018
In accordance with the application (with or without auxiliary actuator) and the type of
fuel, the auxiliary actuator can be activated, deactivated or – in connection with the
LMV50 / LMV51.3 – be used as a VSD and/or auxiliary actuator 3 for the flue gas
recirculation function (refer to chapter
Actuator addresses
).
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
RatioControl
GasSettings
AirActuator
AuxActuator
GasActuator
OilSettings
AirActuator
AuxActuator
OilActuator
The actuators can be activated and deactivated in accordance with the application and
the type of fuel. Here, it is also defined whether the relevant actuator is used for
regulating the air volume. The definition of air-regulating actuators is required for
applications employing VSD and O2 trim control.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
RatioControl
GasSettings
AirActuator
AuxActuator 1
AuxActuator 2
AuxActuator 3
VSD
GasActuator
OilSettings
AirActuator
AuxActuator 1
AuxActuator 2
AuxActuator 3
VSD
OilActuator
For the configuration of VSDs, refer to chapter
Configuring the VSD
.
7. LMV50/LMV51.
activating and
deactivating the
actuators
LMV52
LMV50 / LMV51.3 and
LMV52.2