![Siemens LMV50 series Скачать руководство пользователя страница 280](http://html.mh-extra.com/html/siemens/lmv50-series/lmv50-series_manual_375990280.webp)
280/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
19 O2 trim control with LMV52 and PLL52
22.05.2018
19.10.3 Setting the user-defined type of fuel
If, when firing on gas or oil, the user-defined fuel type is selected, the relevant fuel
parameters must be manually set.
Parameter V_LNmin
Amount of air required for stoichiometric combustion (
κ
= 1) [m³ air per m³ gas] or [m³
air per kg oil]. This value is used for calculating O2 trim control / precontrol.
Parameter V_afNmin
Flue gas volume «wet» with stoichiometric combustion (
κ
= 1) in [m³ flue gas «wet» per
m³ gas] or in [m³ flue gas «wet» per kg oil]. This value is used for calculating O2 trim
control / precontrol or the combustion efficiency.
Parameter V_atrNmin
Flue gas volume «dry» with stoichiometric combustion (
κ
= 1) in [m³ flue gas «dry» per
m³ gas] or in [m³ flue gas «dry» per kg oil]. This value is used for calculating O2 trim
control / precontrol or the combustion efficiency.
Parameter A2
This value is used for calculating the combustion efficiency. It is in compliance with the
definition given in the first BimScHV.
Parameter B/1000
This value is used for calculating the combustion efficiency. It is in compliance with the
definition given in the first BimScHV. The parameters are set using a resolution of
1/1000. This means that a parameterized value of 8 corresponds to 0.008.
Natural
gas H
Natural
gas L
Propane
Butane
Light oil
Heavy oil
V_Lnmin
9.90
8.41
23.80
30.94
11.20
10.73
V_afNmin
10.93
9.43
25.80
33.44
12.02
11.39
V_atrNmin
8.89
7.69
21.80
28.44
10.53
10.08
A2
0.66
0.66
0.63
0.63
0.68
0.68
B/1000
9
≡
0.009
9
≡
0.009
8
≡
0.008
8
≡
0.008
7
≡
0.007
7
≡
0.007
Preset fuel
parameters