Building Technologies
Basic Documentation LMV5...
CC1P7550en
5 Sequence diagrams
22.05.2018
Signal ON Signal OFF
Next phase
01
00, repetition = 0
12, repetition > 0
Parameter
NormalDirectstart
Checking with controller ON
Deviation
↑
10
No repetition decrement
10
70
Without valve proving
↑
70
With valve proving
↑
80
62
Stop, upto phase maximum time
↑
01
0...3 s
Stop, upto phase maximum time
↑
10
Output OFF / input Don’t care
Output ON / input ON
Permissible positioning range
In Standby: actuator can travel within the permissible positioning range, but is always driven
to the home position. Must be in the home position before changing the phase
0°
Position as supplied (0°)
90°
Actuator fully open (90°)
Legend to the sequence diagrams
(cont’d)