9 Commissioning instructions for the LMV5
22.05.2018
Example:
Point
1
2
3
4
5
Order of setting
5
4
3
2
1
Output
15%
28%
50%
71%
100%
Gas
8.6°
28.0°
43.0°
62.5°
81.5°
Air
10.5°
28.8°
46.0°
55.7°
70.8°
AUX
20.3°
30.0°
45.0°
52.0°
60.0°
90
80
70
60
50
40
30
20
10
0
0
10
20
30
40
50
60
70
80
90
100 %
Fuel / air ratio control
Load [%]
P
o
s
it
io
n
[°
]
Gas actuator position
Air actuator position
Auxiliary actuator
7
55
0
d
2
6
E
/0
5
0
2
Figure 81: Fuel-air ratio control
The curvepoints can be changed either during burner off periods (phase 12) or during
burner operation (phase 60).
To change an existing curve, select the curvepoint in
Point
mode. You are now able to
change the point, or to cancel it.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
RatioControl
GasSettings
CurveParams
*) Point
*) Manual
*) Not a parameter name, but a term of curve parameterization
Changing an existing curve