Basic Documentation LMV5...
CC1P7550en
7 Boiler controller / load controller
22.05.2018
Example 1: Reaction thresholds
Q2
and
Q3
for switching stages 2 and 3 on are not
reached. In this case, stage 1 is already switched off when threshold
W+SD_Stage3Off
is reached (low-fire operation).
R=ON
Stage1
Stage 3
Setpoint
Actual value
7550f09E/0502
SD_Stage1Off
W
SD_Stage2Off
SD_Stage3Off
SD_Stage1On
Stage 2
Figure 57: Multistage control – function diagram 1
Example 2: Reaction thresholds
Q2
and
Q3
for switching on stages 2 and 3 are
exceeded and the stages are switched on.
In this case, stage 1 is switched off when threshold
W+ SD_Stage1Off
is
reached.
R=ON
Stage 1
Stage 3
Q2
Q3
Setpoint
Actual value
Q2
Q3
7550f10E/0502
SD_Stage1Off
W
SD_Stage2Off
SD_Stage3Off
SD_Stage1On
Stage 2
Figure 58: Multistage control – function diagram 2
Function diagrams