313/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
22 Revision history
22.05.2018
Burner shutdown at <5 mA not used.
<3 mA: Line interruption
Load output, multistage:
Burner off:
4 mA
Stage 1:
5 mA
Stage 2:
10 mA
Stage 3:
15 mA
22.2.2.2 Load controller, Software from V01.50 to V01.60
The following changes have been introduced:
Plausibility check at inputs X61 and X62
The plausibility check at inputs X61 and X62 is not made anymore. This means that fast
value changes at these inputs will no longer result in safety shutdown.
22.2.2.3 Load controller, Software from V01.60 to V01.80
1. Analog inputs 2 and 3 (X61, X62) were extended by the ranges DC 0…10 V and
0…20 mA.
2. Analog output was extended by the range 0…20 mA.
3. Now, the value presented at the analog output (e.g. load, temperatures, O2, etc.)
can be selected.
4. Introduction of measuring range up to 850 °C (1562 °F) for Pt100, Pt1000 and
Ni1000 temperature input.
5. Inputs 2 (X61) and 3 (X62) also with DC 0...10 V range.
6. Implementation of a variable temperature range.
7. The minimal step for burner output
Minimum actuator step
also becomes active for
external load controllers.
8.
22.2.2.4 Load controller, Software from V01.80 to V02.10
1. Cold start
thermal shock protection.
The starting point for
thermal shock protection
was increased from 0% output to
minimum output.
At the end of
thermal shock protection,
the load controller is initiated with the current
output.
After
thermal shock protection, the LMV5
does not move to low-fire and not back up
again.
2. Extra temperature sensor.
At the end of the thermal shock protection program, the current temperature
acquired by the Ni/Pt1000 sensor programmed as an extra sensor is now updated.
The change only applies to the Ni/Pt1000 sensor, not to the Ni/Pt100 sensor.
The temperature is displayed by the AZL52 / Modbus.
3. Change in connection with temperature-compensated flue gas recirculation (FGR).
In the event of a fault in the Pt / Ni1000 sensor and the operating mode
Flue Gas
Recirc.→ auto deact
, no lockout is initiated.
22.2.2.5 Load controller, software for 2012/2013 release upgrade
For the 2012/2013 release upgrade for the LMV5, the internal load controller's software was
not
changed, meaning that the
V02.10
version is still current.