221/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
13 Mounting , electrical installation and service
22.05.2018
AGG5.631(cable type 2)
AGG5.641(cable typep 1)
1 x SQM45...
2 x SQM45...
3
3 x SQM45...
4 x SQM45...
5
2 x SQM45... + 1 x SQM48...
8
3 x SQM45... + 1 x SQM48...
6
1 x SQM45... + 1 x SQM48...
M
a
xi
m
um
ca
bl
e
le
ng
th
in
m
Cross-section area in
for AC1 and AC2
75
5
0d
13
e/
1
01
2
Figure 102: CAN bus connection between transformer and actuator group
Example:
- System cable:
AGG5.641 (1.25 mm² cross-sectional area)
- Actuators:
2 x SQM45
The point of intersection of the vertical line for the AGG5.641 (1.25 mm
2
) and curve
‚
(2 x SQM45) gives a maximum cable length of 33.4 m between the transformer and the
group of actuators.
Β
Note!
For additional connection of a PLL52, the maximum permissible cable length is
reduced by 2 m.
Diagram 1 for cable length
SQM45 / SQM48