Basic Documentation LMV5...
CC1P7550en
6 Fuel-air ratio control (FARC)
22.05.2018
6.6.6 Overload protection
If the actuators block, lockout is enforced.
However, if the actuators cannot reach the positions required by lockout, they would be
damaged due to overtemperatures.
To prevent this, the actuators are deactivated after a maximum time of 35 seconds, or
at 20% above the value parameterized for
TmeNoFlame
.
Refer to chapter
Displays and settings / special function curve adjustment fuel-air ratio
control.
Curve adjustment