108/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
7 Boiler controller / load controller
22.05.2018
7.4 Control (characteristics)
The load controller can operate in 2 different operating modes:
∂
Modulating, or
∂
Multistage
With electronic fuel-air ratio control, modulating or multistage mode must be selected,
depending on the type of burner.
Parameter
Operation Mode (Two-stage / Three-stage / Modulating)
7.4.1 Integrated 2-position controller (R = ON/OFF)
The integrated 2-position controller transmits to the burner control section the internal
information
Heat request controller
(R = ON/OFF).
Modulating mode:
R = ON when:
Actual value
′
(setpoint ± SD_ModOn)
R = OFF when:
Actual value > (se SD_ModOff)
Multistage mode:
R = ON when:
Actual value
′
(setpoint ± SD_Stage1On)
R = OFF when:
Actual value > (se SD_Stage1Off) or
R = OFF when:
Actual value > (se SD_Stage3Off) = low-fire operation;
always applies if none of the 2 thresholds
Q2
and
Q3
has been
exceeded
Β
Note!
The following standards also have to be observed for multistage operating mode:
∂
SD_Stage3Off
>
SD_Stage1On
∂
SD_Stage3Off
<
SD_Stage2Off
<
SD_Stage1Off
Ι
Note!
When
SD_*_On
is positive, the switching differential lies above the setpoint. When
SD_*_On
is negative, it lies below the setpoint (load controller software version V01.40
or higher).
Parameter SD_ModOn
SD_ModOff
SD_Stage1On
SD_Stage1Off
SD_Stage2Off
SD_Stage3Off
Operating mode
General
Switching differentials