175/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
9 Commissioning instructions for the LMV5
22.05.2018
To create a new curvepoint, select
Manual
. Set the output of the new point and
acknowledge by pressing
Enter
.
During the manual action, the actuators travel on the interpolated straight lines between
the curvepoints.
After pressing
Enter
, each individual actuating device can be selected to optimize the
position.
To leave the curvepoint setting, press the
Esc
button or store the point by pressing
Enter
.
Finally, you can limit the burner output to a minimum and maximum in accordance with
the boiler’s requirements.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
RatioControl
GasSettings
LoadLimits
MinLoadGas
MaxLoadGas
Select
Autom/Manual/Off
and then
Burner off
.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
ManualOperation
Autom/Manual/Off
Creating a new curvepoint
16. Load limits
17. Shutdown