171/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
9 Commissioning instructions for the LMV5
22.05.2018
9.2 Settings for gas-fired operation
The next steps explain how the fuel-air ratio control system is to be set.
Specific curves are required for each type of fuel.
Activate a program stop when startup shall be stopped to set the special positions.
Prepurging
Phases 24…34
Ignition position
Phase 36
Interval 1
Phase 44
Interval 2
Phase 52
Postpurging
Phases 72…78
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
RatioControl
ProgramStop
deactivated
24PrePurgP
32PreP FGR
36IgnitPos
44Interv1
52Interv2
72PostPPos
76PostPFGR
Activate a program stop in phase 24.
The unit is supplied with presettings of the parameters
HomePos, PrepurgePos
and
PostpurgePos
. These positions should be checked and adapted if required, either now or
during the following program stops.
The ignition positions are
not
predefined. In this section, a valid setting must be made
or, otherwise, burner startup is
not
possible.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
RatioControl
GasSettings
SpecialPositions
IgnitionPos
IgnitionPosGas
IgnitionPosAir
IgnitionPosAux1
IgnitionPosAux2
Only LMV52
IgnitionPosAux3
IgnitionPosVSD
LMV50/LMV51.3/
LMV52
Example:
Gas actuator: 32.5°
Air actuator: 25.6°
To start the burner, select
Autom/Manual/Off
and then
Manual
.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
ManualOperation
Autom/Manual/Off
If startup shall be watched, press simultaneously selection buttons «
<
» and «
>
» to
switch the display to
Normal operation
.
10. Activating program
stops in different
program phases
11. Checking and
presetting the actuator
positions for gas ignition
12. Manual startup