245/327
Building Technologies
Basic Documentation LMV5...
CC1P7550en
18 VSD module
22.05.2018
18.1.5 Configuring the current interface
The VSD is controlled via a current interface which can be switched from 0...20 mA to
4...20 mA, or vice versa.
Β
Note!
If the VSD requires an input signal of DC 0...10 V, a resistor of 500
ς °
1% must be
connected parallel to its input.
18.1.6 Configuring the fuel meter
The module can be used with fuel meters having a Namur or Reed output or open
collector (pnp).
To be able to adapt the module to different types of meters, the number of pulses
corresponding to a volume unit must be parameterized in the system.
The setting requires 4 or 5 decimal points. If
one
of these values shall be changed, the
following setting procedure is required on the following menu:
Params & Display
↑
VSD Module
↑
Configuration
↑
Fuel Meter
↑
Pulse Value Gas
or
Params & Display
↑
VSD Module
↑
Configuration
↑
Fuel Meter
↑
Pulse Value Oil
The pointer indicates the unit to be selected (1 m
3
/1 ft
3
).
Parameter Analog
Output
P
u
l
s
e
V
a
l
u
e
G
a
s
C
u
r
r
:
3
.
0
0
0
0
1
m
3
=
3
.
0
0
0
0
The proposed unit can be changed by pressing
Select
.
When pressing
Enter
, the pointer jumps to the first position of the display section with
the numbers.
P
u
l
s
e
V
a
l
u
e
G
a
s
C
u
r
r
:
3
.
0
0
0
0
1
m
3
=
3
.
0
0
0
0
Select
can be used to change the digit with the highest value of the numerical number,
or
Enter
can be pressed to switch to the next digit.
After selecting the last decimal place and pressing
Enter
, the value is adopted.
Press
Esc
to exit the menu.
The setting procedure for
Pulse Value Oil
is the same as that for
Pulse Value Gas
, the
selectable units being 1 l or 1 gal.
Pulse value gas
Pulse value oil