5.2.5 Operation of monitoring parameters
1) In the initial state (0 level menu), press the MENU button, it will display the current function
group number A0;
2) Press SHIFT one times and shift the flasher to the bit of A;
3) Turn the knob clockwise and change A to U;
4) Press ENTER to display U0-00;
5) Press ENTER to display the value of the current function code U0-00, 0.40;
6) Press ENTER, it will display U0-01;
7) Press ENTER again, it will display the value of the current function code U0-01 0;
8) Press MENU button to display the U0-01 function code;
9) Press MENU button again, it will display the U0 function code group number;
10) Press the MENU button, it will back to the initial display state;
Fig.5-7 Monitoring Parameters viewing procedure