SV800/SV800A User Manual 7 Detailed function description
193
No.
Name
Set range
Factory default
H2-03
AI2 range selection
0
~
1
0
0:0~10V
The negative input signal is limited to 0V.
1:-10V~10V
The gain and bias set in H2-04 and H2-05.
No.
Name
Set range
Factory default
H2-04
AI2 gain setting
-300.0%
~
300.0%
100.0%
H2-05
AI2 bias setting
-300.0%
~
300.0%
0.0%
100.0% relating to 10V signal.
No.
Name
Set range
Factory default
H2-09
AI1 filter time
0.000s
~
10.000s
0.100s
H2-10
AI2 filter time
0.000s
~
10.000s
0.100s
Increasing filter time of AI can increase the anti-interference ability, but the response will
become slow.
No.
Name
Set range
Factory default
H2-12
The Min. detection of AI
0.000V
~
1.000V
0.040V
When the
input
AI value less than the value in
H2-12
, it will be regard as 0V.