SV800/SV800A User Manual 6 Function Parameters List
117
F1: Constant pressure water supply
No.
Name
Content
Set value
F1-09
(5109H)
Judgment frequency
when decreasing pump
ALL
Factory default
:
10.00Hz
Range
:
E0-03~F1-08
F1-10
(510AH)
Add pump delay time
ALL
Factory default
:
10.0s
Range
:
0.0s~999.9.0s
F1-11
(510BH)
Decrease pump delay
time
ALL
Factory default
:
5.0s
Range
:
0.0s~999.9s
F1-12
(510CH)
Contactor control delay
time
ALL
Factory default
:
0.5s
Range
:
0.1s~10.0s
F1-13
(510DH)
Automatic
switching
delay time
ALL
Factory default
:
0Min
Range
:
0Min~65535Min
F1-14
(510EH)
Sleep pressure judgment
range
ALL
Set by the range of the pressure gauge or pressure sensor
Factory default
:
0%
Range
:
0%~20.0%
F1-15
(510FH)
Water shortage protection
ALL
0: No protection
1: With sensor water shortage protection
2: Without sensor water shortage protection
Factory default
:
0
Range
:
0~2
F1-16
(5110H)
Water shortage protection
current
ALL
When F1-15=2, the output current threshold of judging water
shortage
Factory default
:
80%
Range
:
10%~150%
F1-17
(5111H)
Wake-up delay time after
water shortage protection
ALL
Factory default
:
60Min
Range
:
0Min~3000Min
F1-18
(5112H)
Water shortage protection
judgment delay time
ALL
Factory default
:
2.0s
Range
:
0.0s~10.0s
F2:Paper towel equipment parameters
No.
Name
Content
Set value
F2-00
(5200H)
Enable Non-standard
ALL
0: Invalid
1:Valid
Factory default
:
0
Range
:
0~1
F2-01
(5201H)
Filter coefficient
ALL
Factory default
:
0.300
Range
:
0.000~2.000