SV800/SV800A User Manual 7 Detailed function description
197
7.7 L:Communication parameters
Modbus communication parameters set in L group.
7.7.1 L0:Basic communication parameters
No.
Name
Set range
Factory default
L0-00
Baud rate selection
0
~
5
2
0
:
4800bps
1
:
9600bps
2
:
19200bps
3
:
38400bps
4
:
57600bps
5
:
115200bps
No.
Name
Set range
Factory default
L0-01
Data format
0
~
2
0
0: No parity (8-N-1)
1: Even parity (8-E-1)
2: Odd parity (8-O-1)
No.
Name
Set range
Factory default
L0-02
Local address
0
~
247
1
0 is the broadcast address, available address 1~247.
No.
Name
Set range
Factory default
L0-03
Response delay
1ms
~
20ms
5ms
The response delay time of the inverter to the upper device.
No.
Name
Set range
Factory default
L0-04
Communication timeout
0.0s
~
20.0s
0.0s
The detection time of communication timeout. When it’s 0, function is invalid.
No.
Name
Set range
Factory default
L0-05
Communication mode selection
0
~
1
0
0:Modbus RTU
1:Reserved