SV800/SV800A User Manual 7 Detailed function description
161
The time determined by AI. Voltage signal 0~10V, -10V~+10Vor current signal 0~20mA or
4~20mA can be selected. The Max. range corresponds to the set time in
d2-28
.
3: Reserved
No.
Name
Set range
Factory default
d2-28
Timing of Runtime
0.0
~
6500.0min
0.0min
Refer to
d2-27
.
No.
Name
Set range
Factory default
d2-29
Arrival time setting for this operation
0.0
~
6500.0min
0.0min
When the runtime arrives at the set value and the multi-function output terminal selected the run
time arrival function, it outputs "the run time arrival" ON signal.
No.
Name
Set range
Factory default
d2-30
Mechanical speed coefficient
0.1%
~
999.9%
100.0%
The set mechanical speed and output mechanical speed can be monitored in parameters U0-31
and
U0-32
,
the formula as follows:
The set mechanical speed
U0-31
=120 *
U0-00
*
d2-30
/ Number of motor poles
The output mechanical speed
U0-32
=
U0-01
*
d2-30
No.
Name
Set range
Factory default
d2-31
Line speed coefficient
0.1%
~
999.9%
100.0%
The set line speed and output line speed can be monitored in parameters U0-33 and U0-34, the
formula as follows :
The set line speed
U0-33
=120 *
U0-00
×
d2-31
/60/ Number of motor poles
The output line speed
U0-32
=
U0-01
×
d2-31
/60