SV800/SV800A User Manual 7 Detailed function description
201
When fault occurs,
the
inverter will reset fault automatically after delay time set in
P0-14
until
the self-recovery times exceeds the value in
P0-13
. The function is invalid when it’s 0.
Note: Inverter overheat, motor overheat, IGBT protection, motor self-learning fault cannot be self-recovery.
No.
Name
Set range
Factory default
P0-15
Relay action selection when automatic fault
reset
0
~
1
0
When fault self-
recovery
function selected, the fault relay action can be set in
P0-15
.
0:Relay does not operate
1:Relay action
No.
Name
Set range
Factory default
P0-16
Input loss phase detection filter time
0.0s
~
10.0s
0.0s
It’s the filter for input loss phase detection. The input loss phase detection is invalid when the
value of
P0-16
is 0.
No.
Name
Set range
Factory default
P0-17
Output loss phase detection Enable
0
~
1
0
0:Invalid
1:Valid
V/F control, when not motor connect to U,V,W, it not detect loss phase detection.
No.
Name
Set range
Factory default
P0-18
Fan control selection
0
~
1
0
0: Fan runs when the inverter is in standby
1: Fan not run when the inverter is in standby
The fan control
selection
just suitable for the inverter with power or less than 37KW. For the
inverter with power or above 45KW, the fan not run in standby status.
No.
Name
Set range
Factory default
P0-19
Short circuit relay detection Enable
0
~
1
0
0: Valid
1: Invalid
The detection
function
of bypass relay(Short circuit relay) in the charging circuit.