7 Detailed function description SV800/SV800A User Manual
156
function can not reduce the motor shaft output power required to drive the load as the motor
shaft output power is determined by the external load.
0
:
OFF
1
:
ON
No.
Name
Set range
Factory default
d2-06
Stop mode selection
0
~
2
1
d2-07
Stop speed/frequency
0.00Hz
~
10.00Hz
1.00Hz
d2-08
DC braking time
0.0s
~
30.0s
0.0s
d2-09
DC braking current
20%
~
150%
100%
d2-06 (Stop mode selection).
0: Free stop
When the stop command input or the JOG command is canceled, the inverter blocks the output
and the motor stops freely.
1: Deceleration stop
When the stop command input or the JOG command is canceled, the inverter will stop output
voltage after decelerating to d2-07 (stop speed/frequency) according to the set deceleration
time.
2: Decele DC brake stop
When the stop command input or jog command is canceled, it will decelerate to d2-07 (stop
speed/frequency) according to the set deceleration time and then enter the DC braking mode
from AC mode. The braking time is set in d2-08 (DC braking time). In vector control, the
braking current is set by d2-09 (DC braking current) (100% corresponds to the rated motor
current). Under V/F control, the braking voltage set by d4-02 (DC braking voltage) (100.0%
corresponds to the rated voltage).
The stop mode is shown in
Fig. 7-4
.
Fig. 7 - 4 Stop mode
Note: Except for speed control mode, for others mode selected in d2-00, regardless of the d2-06 setting, the
stop mode is free stop.
n
r
r
max
r
max
n
n
t
t
t
t
t
t
n
Current amplitude
Current
amplitude
n
i
i
i
i
i
t
t
d2-07
Command
Stop
d2-06=2
Command
Stop
max
Run
Run
d2-09
d2-08
n
t= Dec. Time
Stop
Run
Coast Stop
d2-06=1
Current
amplitude
i
d2-06=0
t
Command