SV800/SV800A User Manual 7 Detailed function description
173
7.5 F:Application function parameters group
7.5.1 F0: PID control parameters
No.
Name
Set range
Factory default
F0-00
Closed-loop operation control selection
0
~
1
0
0: Invalid
1: Universal PID control valid
No.
Name
Set range
Factory default
F0-01
PID given Channel selection
0
~
6
0
0:
Parameter setting (F0-02)
The PID target value set by
F0-02
.
1: AI1 analog input
2: AI2 analog input
The PID target value determined by AI. The AI signal can be 0~10V, -10V~+10V voltage signal
or 0~20mA, 4~20mA current signal. The Max. range corresponds to 100.0%.
3: Reserved
4: Pulse setting HDI
The PID target value adjusted by HDI high speed pulse.
0KHz~100KHz available, high speed pulse signal can only be connected to HDI terminal.
5: Communication setting
The PID target value set by the upper devices through Modbus communication.
6: Multiple instructions setting
The PID target value set by E1-00~E1-15,it’s percentage value of the multi-speed command
relating to
E0-00
.
No.
Name
Set range
Factory default
F0-02
PID target value setting
0.0%
~
100.0%
50.0%
The PID target value set by F0-02 when F0-01= 0.
No.
Name
Set range
Factory default
F0-03
PID feedback channel selection
0
~
7
0
0: AI1 analog input
1: AI2 analog input
The PID feedback determined by AI. The AI signal can be 0~10V, -10V~+10V voltage signal or
0~20mA, 4~20mA current signal. The Max. range corresponds to 100.0%.
2: Reserved