6 Function Parameters List SV800/SV800A User Manual
114
F0: PID control parameters
No.
Name
Content
Set value
F0-07
(5007H)
Integration time Ti1
ALL
Factory default
:
2.00s
Range
:
0.01s~10.00s
F0-08
(5008H)
Differential time Td1
ALL
Factory default
:
0.000s
Range
:
0.000s~10.000s
F0-09
(5009H)
PID differential limit
ALL
Factory default
:
0.10%
Range
:
0.00%~100.00%
F0-10
(500AH)
PID deviation limit
ALL
Factory default
:
0.0%
Range
:
0.0%~20.0%
F0-11
(500BH)
PID reverse cutoff speed
/ frequency
ALL
Factory default
:
0.00Hz
Range
:
0.00Hz~[E0-02]
F0-12
(500CH)
PID setting filter time
ALL
Factory default
:
0.00
Range
:
0.00~600.00s
F0-13
(500DH)
PID feedback filter time
ALL
Factory default
:
0.00s
Range
:
0.00s~60.00s
F0-14
(500EH)
PID output filter time
ALL
Factory default
:
0.00s
Range
:
0.00s~60.00s
F0-15
(500FH)
Proportional gain KP2
ALL
Factory default
:
20.0
Range
:
0.0~100.0
F0-16
(5010H)
Integration time Ti2
ALL
Factory default
:
2.00s
Range
:
0.01s~10.00s
F0-17
(5011H)
Differential time Ti2
ALL
Factory default
:
0.000s
Range
:
0.000s~10.000s
F0-18
(5012H)
PID initial value
ALL
Factory default
:
0.0%
Range
:
0.0%~100.0%