![SCOV SV800 Series Скачать руководство пользователя страница 238](http://html.mh-extra.com/html/scov/sv800-series/sv800-series_user-manual_1219567238.webp)
Appendix D: A1 application selection and parameter mapping SV800/SV800A User Manual
230
Appendix D: A1 application selection and parameter
mapping
In order to
facilitate
the user to set the parameters using the SV800A/SV800 series, as long as
the user selects the inverter application in A1-00, A1-01 ~ A1-49 will automatically correspond
to the function parameters and arranged according to the application frequency.
A1: Customer application parameters
No.
Name
Contents
Set value
A1-00
(0100H)
Application selection
ALL
0: User defined
1: General speed regulation
2: Air supply / exhaust fan
3: Constant pressure water supply (one inverter with
one pump or one inverter two pumps)
4~20: Reserved
Factory default:1
Range:0~20
D.1 Application of general speed regulation (A1-00 = 1)
No.
Name
Factory default
Description
Mapping
parameter
A1-01
Control mode setting
2: V/F control
0: SVC vector control <1>
A0-04
A1-02
Run command input
selection
0: Keyboard control
1: Terminal control
2: Communication control
d1-00
A1-03
Main
frequency
command
input
selection
0: Keyboard parameter
(E1-00 ) setting (Keyboard
potentiometer valid)
1:
Keyboard
parameter
(E1-00 ) setting (keyboard
potentiometer invalid)
2: AI1
3~9: Refer to the detailed
description
d1-01
A1-04
Frequency 1
50.00Hz
E1-00
A1-05
Acc. time 1
Determined
with
the
model
Set
according
to
requirements
E2-02
A1-06
Dec. time 1
Determined
with
the
model
Set
according
to
requirements
E2-03
A1-07
DI1 terminal function
selection
3: Forward running
Other options look at the
detailed
description
of
Chapter 7.
H0-00
A1-08
DI2 terminal function
selection
4: Reverse running
Other options look at the
detailed
description
of
Chapter 7.
H0-01
A1-09
M1
relay
output
function selection
35: Running (including
DC braking)
Other options look at the
detailed
description
of
Chapter 7.
H1-03
A1-10
TA-TB-TC relay input
17: In failure
Other options look at the
H1-13