SV800/SV800A User Manual 7 Detailed function description
195
For the setting method, please refer to the information in
H3-02
and
H3-03
.
No.
Name
Set range
Factory default
H3-09
AO2 filter time
0.00s
~
10.00s
0.10s
Table 7-5 Analog output function
Set value
Function
Range
0
No function
1
The set speed command
0~ Upper limit speed/frequency
2
Motor speed
0~ Upper limit speed/frequency
3
Inverter output frequency
0~ Upper limit speed/frequency
4
Inverter output current
0~2 times motor rated current
5
Inverter output voltage
0~ motor rated voltage
6
DC bus voltage
0.0~1000.0V
7
Torque command
0%~300%
8
AI1 input signal (Converted to voltage)
0.00~10.00V
9
AI2 input signal (Converted to voltage)
0.00~10.00V
10
AI3 input signal (Converted to voltage)
0.00~10.00V
11
Input pulse frequency
0~H4-00
12
Motor output torque
0~Motor Max. output torque
7.6.5 H4: Multi-function pulse input and output
No.
Name
Set range
Factory default
H4-00
Pulse input HDI range setting
0.10KHz
~
100.00KHz
20.00KHz
Used to set the Max. range of high speed pulse input.
No.
Name
Set range
Factory default
H4-01
HDI gain setting
0.0%
~
200.0%
100.0%
H4-02
HDI bias setting
-100.0%
~
100.0%
0.0%
The setting method is same as AI. Please refer to the information in
H2-01
and
H2-02
.
No.
Name
Set range
Factory default
H4-03
HDI input filter time
0.00s
~
20.00s
0.10s
H4-04
HDI Min. input frequency
1Hz
~
10000Hz
1Hz
When the high pulse input frequency less than the set value in
H4-04
, it cannot be sampled
effectively.