SV800/SV800A User Manual 6 Function Parameters List
99
d2: Operating module control parameters
No.
Name
Content
Set value
d2-00
(3200H)
Selection of Motor
Driving Mode
IM.SVC IM.VC
0: Speed Control Mode (ASR)
1: Torque command negative side priority mode
2: Torque command positive side priority mode
3: Torque Control Mode (ATR)
4: Speed / torque control switching mode
Valid in vector control mode, set to 1 or 2 for automatic
switching of speed/torque control.
Factory default
:
0
Range
:
0~4
d2-01
(3201H)
Torque Limit Value of
Forward motoring
IM.SVC IM.VC
Factory default
:
180%
Range
:
0%~300%
d2-02
(3202H)
Torque Limit Value of
Forward regenerating
IM.SVC IM.VC
Factory default
:
-180%
Range
:
-300%~0%
d2-03
(3203H)
Torque Limit Value of
Reverse motoring
IM.SVC IM.VC
Factory default
:
-180%
Range
:
-300%~0%
d2-04
(3204H)
Torque Limit Value of
Forward regenerating
IM.SVC IM.VC
Factory default
:
180%
Range
:
0%~300%
d2-05
(3205H)
High efficiency control
selection
IM.SVC IM.VC
0
:
OFF
1
:
ON
Factory default
:
0
Range
:
0~1
d2-06
(3206H)
Stop mode selection
ALL
0: Free stop
1: Deceleration stop
2: Decele DC Braking Stop
In vector control, if the control mode is torque control, such as
d2-00=1-4, the Stop mode is not restricted by d2-06. When the
stop instruction input, it will free stop.
Factory default
:
1
Range
:
0~2
d2-07
(3207H)
Stop speed/frequency
ALL
Factory default
:
1.00Hz
Range
:
0.00Hz~10.00Hz
d2-08
(3208H)
DC braking time
ALL
Factory default
:
0.0s
Range
:
0.0s~30.0s
d2-09
(3209H)
DC braking current
IM.SVC IM.VC
100% relating to the motor rated current
Factory default
:
100%
Range
:
20%~150%
d2-10
(320AH)
Low limit
speed/Frequency
Operation Mode
ALL
0: Run at the low. limit speed/ frequency
1: Stop by stop mode
2: Sleep
Factory default
:
2
Range
:
0~2