![SCOV SV800 Series Скачать руководство пользователя страница 113](http://html.mh-extra.com/html/scov/sv800-series/sv800-series_user-manual_1219567113.webp)
SV800/SV800A User Manual 6 Function Parameters List
105
E1:Speed/ frequency instructions
No.
Name
Content
Set value
E1-11
(410BH)
Speed/frequency 12
ALL
12
th
speed for multi-speed command and the simple PLC
command
Factory default
:
30.00Hz
Range
:
[-E0-02]~[E0-02]
E1-12
(410CH)
Speed/frequency 13
ALL
13
th
speed for multi-speed command and the simple PLC
command
Factory default
:
40.00Hz
Range
:
[-E0-02]
~[E0-02]
E1-13
(410DH)
Speed/frequency 14
ALL
14
th
speed for multi-speed command and the simple PLC
command
Factory default
:
45.00Hz
Range
:
[-E0-02]
~[E0-02]
E1-14
(410EH)
Speed/frequency 15
ALL
15
th
speed for multi-speed command and the simple PLC
command
Factory default
:
50.00Hz
Range
:
[-E0-02]
~[E0-02]
E1-15
(410FH)
Speed/frequency 16
ALL
16
th
speed for multi-speed command and the simple PLC
command
Factory default
:
50.00Hz
Range
:
[-E0-02]
~[E0-02]
E1-16
(4110H)
Jog speed/frequency
ALL
Factory default
:
0.80Hz
Range
:
[-E0-02]
~[E0-02]
E2:Acc./Dec. time selection
No.
Name
Content
Set value
E2-00
(4200H)
Acc./Dec. time selection
during operation
ALL
0:
Acc./Dec. time
1
1:
Acc./Dec. time
2
2:
Acc./Dec. time
3
3:
Acc./Dec. time
4
Factory default
:
0
Range
:
0~3
E2-01
(4201H)
Acc./Dec. time selection
for JOG operation
ALL
0:
Acc./Dec. time
1
1:
Acc./Dec. time
2
2:
Acc./Dec. time
3
3:
Acc./Dec. time
4
Factory default
:
1
Range
:
0~3
E2-02
(4202H)
Acc. time 1
ALL
The Acc. Time to accelerate from 0.00Hz to E0-02.
Acc. time of 1
st
speed in Multi-speed control.
Factory default
:
Determined with
the model
Range
:
0.0s~3600.0s
E2-03
(4203H)
Dec. time 1
ALL
The Dec. Time to decelerate E0-02 to 0.00Hz.
Dec. time of 1
st
speed in Multi-speed control.
Factory default
:
Determined with
the model
Range
: