3 Mechanical Installation
3.1 Mechanical Installation
3.1.1 Installation Environment
Please install the inverter according to the below
Table 3-1
.
Table 3-1 Installation Environment
Item
Requirements
Installation place
Indoor
Ambient
temperature
-10 to +40 °C
Please use it in the place where the temperature does not change drastically.
When using it in a closed space such as a control cabinet, please use cooling fan or
cooling air conditioner to cool it and prevent the internal temperature from
exceeding the condition temperature.
Please avoid the inverter freezing.
Humidity
95% RH or below
Please avoid condensation on the inverter.
Storage
temperature
-20
~
+60°C
Environment
Locations free from oil mist, corrosive gases, flammable gases, dust, etc.
Locations that metal powder, oil, water and other external objects can not enter the
inverter.(Do not install the inverter on flammable materials such as wood.)
Location without radioactive materials and flammable materials
Place without harmful gases and liquids
Place with less salt erosion
Place without direct sunlight
Altitude
Less than 1000m,
derating 1% for each 100 meters when higher than 1000m.
<1>
Note 1: Please do not install transformers or other equipments around the inverter which generate
electromagnetic waves or interference, otherwise it will cause the inverter to malfunction. If you need to
install such equipment, you should install shield plate before the inverter.
Note 2: Please use cloth or paper to cover the upper portion of the frequency inverter to prevent metal
debris, oil and water from entering into the frequency inverter during installation. After finish the job, be
sure to remove the cloth or paper, and if it still covered, the ventilation will become poor and causes the
frequency inverter to abnormally heat.