![SCOV SV800 Series Скачать руководство пользователя страница 174](http://html.mh-extra.com/html/scov/sv800-series/sv800-series_user-manual_1219567174.webp)
7 Detailed function description SV800/SV800A User Manual
166
No.
Name
Set range
Factory default
E2-00
Acc./Dec. time selection during operation
0
~
3
0
E2-01
Acc./Dec. time selection for JOG operation
0
~
3
1
0: Acc./Dec. time 1
Set by
E2-02
and
E2-03
.
1:
Acc./Dec. time
2
Set by
E2-04
and
E2-05
.
2:
Acc./Dec. time
3
Set by
E2-06
and
E2-07
.
3:
Acc./Dec. time
4
Set by
E2-08
and
E2-09
.
No.
Name
Set range
Factory default
E2-02~
E2-24
Acc./Dec. time 1 ~ Acc./Dec. time 16
0.0s
~
3600.0s
Determined with the
model
Acc. time is defined as the time needed for increasing frequency from 0.00Hz to
E0-02
, Dec.
time is defined as the time needed for decreasing frequency from
E0-02
to 0.00Hz. Factory
default Acc./Dec. time set in
E2-02
,
E2-03
, Jog Acc./Dec. time set in
E2-04, E2 -05
. When
multi-speed selected, each speed has its own independent Acc./Dec. time, like 1
st
speed
corresponds to Acc./Dec. time 1. For UP/DOWN function, the change rate of the UP or DOWN
frequency command determined by Acc./Dec. time 4 (
E2-08, E2-09
).
No.
Name
Set range
Factory default
E2-34
S curve Enable
0
~
1
0
0:OFF
1:ON
S curve is valid.
The specific time setting of S curve is determined by the multi-function input terminal "S curve
Acc./Dec. time 1/2 selection".
No.
Name
Set range
Factory default
E2-35
S curve Acc. start time 1
0.0s
~
60.0s
0.1s
E2-36
S curve Acc. arrival time 1
0.0s
~
60.0s
0.1s
E2-37
S curve Dec. start time 1
0.0s
~
60.0s
0.1s
E2-38
S curve Dec. arrival time 1
0.0s
~
60.0s
0.1s
E2-39
S curve Acc. start time 2
0.0s
~
60.0s
0.1s
E2-40
S curve Acc. arrival time 2
0.0s
~
60.0s
0.1s
E2-41
S curve Dec. start time 2
0.0s
~
60.0s
0.1s
E2-42
S curve Dec. arrival time 2
0.0s
~
60.0s
0.1s