Appendix D: A1 application selection and parameter mapping SV800/SV800A User Manual
234
D.3 Application of constant pressure water supply (one inverter
with one pump or one inverter two pumps) (A1-00=3)
No.
Name
Factory default
Description
Mapping
parameter
A1-01
Control
mode
setting
2: VF control
V/F control for general using
A0-04
A1-02
G/P
model
selection
0: G type
1:P type
A0-12
A1-03
Run
command
input selection
0: Keyboard control
1: Terminal control
2: Communication control
d1-00
A1-04
Main
frequency
command
input
selection
0:
Keyboard
parameter
(E1-00) setting (keyboard
potentiometer valid)
8: PID
Refer to Chapter 7 for details
d1-01
A1-05
Acc. time 1
Determined with the model
Set according to requirements
E2-02
A1-06
Dec. time 1
Determined with the model
Set according to requirements
E2-03
A1-07
DI1 function
3: Forward running
Refer to Chapter 7 for details
H0-00
A1-08
Closed-loop
operation
control
selection
0: Invalid
Need to be set to 1: Universal
PID control valid
F0-00
A1-09
PID given channel
selection
0: Parameter setting given
(F0-02)
Refer to Chapter 7 for details
F0-01
A1-10
PID
feedback
channel selection
0: AI1 analog input
Refer to Chapter 7 for details
F0-03
A1-11
Constant pressure
water supply mode
selection
0: Invalid
1: One Inverter one Pump
2: One Inverter two Pumps
F1-00
A1-12
Target
pressure
setting
0.20MPa
Set according to actual needs
F1-01
A1-13
Pressure range
1.00MPa
According to the actual remote
pressure gauge or sensor
settings
F1-02
A1-14
AI1 signal type
0
:
0~10V
1:4~20mA (S2 switch needs to
be switched to current gear)
H2-00
A1-15
Start
mode
selection
1:
Start
from
Min.
frequency (E0-03)
Generally set to 0: Start by
speed tracking
d4-04
A1-16
Stop
mode
selection
1: Deceleration stop
0: Free stop
d2-06
A1-17
Torque boost
Determined with the model
Generally set to 0%
d4-01
A1-18
Sleep frequency
30.00Hz
Factory default sleep, wake-up
function is invalid, generally
F1-03
A1-19
Sleep delay time
0.0s
F1-04