![SCOV SV800 Series Скачать руководство пользователя страница 132](http://html.mh-extra.com/html/scov/sv800-series/sv800-series_user-manual_1219567132.webp)
6 Function Parameters List SV800/SV800A User Manual
124
H3: Multi-function analog output AO
No.
Name
Content
Set value
H3-00
(7300H)
Multi-function AO1
function selection
ALL
0: No function
1: The set speed command
2: Motor speed
3: Inverter output frequency
4: Inverter output current
5: Inverter output voltage
6: DC bus voltage
7: Torque command
8: AI1 input signal(Converted to voltage)
9: AI2 input signal(Converted to voltage)
10: AI3 input signal(Converted to voltage)
11: Input pulse frequency
12: Motor output torque
Factory default
:
3
Range
:
0~12
H3-01
(7301H)
Multi-function AO1
range selection
ALL
0:0~10V
1:Reserved
2:4~20mA
Factory default
:
0
Range
:
0~2
H3-02
(7302H)
AO1 gain setting
ALL
-300.0 ~ 300.0%(100% relating to 10V of AO1)
Factory default
:
100.0%
Range
:
-300.0%~300.0%
H3-03
(7303H)
AO1 bias setting
ALL
0.0 ~ 300.0%(100% relating to 10V of AO1)
Factory default
:
0.0%
Range
:
0.0%~300.0%
H3-04
(7304H)
AO1 filter time
ALL
0.00
~
10.00
Factory default
:
0.10s
Range
:
0.00s~10.00s
H3-05
(7305H)
Multi-function AO2
function selection
ALL
Please refer to the functions in "
H3-00
"
Factory default
:
0
Range
:
0~12
H3-07
(7307H)
AO2 gain setting
ALL
-300.0 ~ 300.0%(100% relating to 10V of AO2)
Factory default
:
100.0%
Range
:
-300.0%~300.0%
H3-08
(7308H)
AO2 bias setting
ALL
0.0 ~ 300.0%(100% relating to 10V of AO2)
Factory default
:
0.0%
Range
:
0.0%~300.0%
H3-09
(7309H)
AO2 filter time
ALL
0.00
~
10.00
Factory default
:
0.10s
Range
:
0.00s~10.00s