SV800/SV800A User Manual 6 Function Parameters List
113
E4: Simple PLC and multi-speed
No.
Name
Content
Set value
E4-22
(4416H)
Simple PLC Acc./Dec.
time selection Step
13~16
ALL
Units Digits:
Simple PLC Acc./Dec. time selection of Step 13
0: Acc./Dec. time 1
1: Acc./Dec. time 2
2: Acc./Dec. time 3
3: Acc./Dec. time 4
Tens Digits:
Simple PLC Acc./Dec. time selection of Step 14
(Same as above)
Hundreds Digits:
Simple PLC Acc./Dec. time selection of Step
15 (Same as above)
Thousands Digit:
Simple PLC Acc./Dec. time selection of Step
16 (Same as above)
Factory default
:
0x0000
Range
:
0x0000~0x3333
F0: PID control parameters
No.
Name
Content
Set value
F0-00
(5000H)
Closed-loop operation
control selection
ALL
0:Invalid
1:Universal PID control valid
Factory default
:
0
Range
:
0~1
F0-01
(5001H)
PID given channel
selection
ALL
0: Parameter setting (F0-02)
1: AI1 analog input
2: AI2 analog input
3: Reserved
4: Pulse setting HDI
5: Communication setting (Communication address 0x6003)
6: Multiple instructions setting
Factory default
:
0
Range
:
0~6
F0-02
(5002H)
PID target value setting
ALL
0.0%~100.0%
Factory default
:
50.0%
Range
:
0~100.0%
F0-03
(5003H)
PID feedback channel
selection
ALL
0: AI1 analog input
1: AI2 analog input
2: Reserved
3: AI1+AI2
4: AI1-AI2
5: Max.(|AI1|, |AI2|)
6:Min.(|AI1|, |AI2|)
7: Pulse setting HDI
Factory default
:
0
Range
:
0~7
F0-04
(5004H)
Closed-loop regulation
characteristic
ALL
0: Positive
1: Negative
Factory default
:
0
Range
:
0~1
F0-05
(5005H)
PID target/feedback
range
ALL
Factory default
:
1000
Range
:
0~65535
F0-06
(5006H)
Proportional gain KP1
ALL
Factory default
:
20.0
Range
:
0.0~100.0