![SCOV SV800 Series Скачать руководство пользователя страница 103](http://html.mh-extra.com/html/scov/sv800-series/sv800-series_user-manual_1219567103.webp)
SV800/SV800A User Manual 6 Function Parameters List
95
b2: Second induction motor parameters
No.
Name
Content
Set value
b2-14
(120EH)
Second motor iron loss
conductance
IM.SVC IM.VC
Factory default
:
Determined with
the model
Range
:
0.0mho~600.0mho
b2-15
(120FH)
Second motor loss factor
1
IM.SVC IM.VC
Factory default
:
Determined with
the model
Range
:
0.0% ~200.0%
b2-16
(1210H)
Second motor loss factor
2
IM.SVC IM.VC
Factory default
:
Determined with
the model
Range
:
0.0% ~200.0%
d0 :Speed control debugging parameters
No.
Name
Content
Set value
d0-00
(3000H)
First motor speed control
proportional gain
IM.SVC IM.VC
Factory default
:
15
Range
:
3~100
d0-01
(3001H)
First motor speed control
integral time constant
IM.SVC IM.VC
Factory default
:
40ms
Range
:
20ms~10000ms
d0-02
(3002H)
First motor speed control
rotation inertia
IM.SVC IM.VC
Factory default
:
10 gm²
Range
:
0 gm²
~65535 gm²
d0-03
(3003H)
Second motor speed
control proportional gain
IM.SVC IM.VC
Factory default
:
15
Range
:
3~100
d0-04
(3004H)
Second motor speed
control integral time
constant
IM.SVC IM.VC
Factory default
:
40ms
Range
:
20ms~10000ms
d0-05
(3005H)
Second motor speed
control rotation inertia
IM.SVC IM.VC
Factory default
:
10 gm²
Range
:
0 gm²
~65535 gm²
d0-09
(3009H)
Torque observer selection
IM.SVC IM.VC
0
:
OFF
1
:
ON
Factory default
:
1
Range
:
0~1
d0-10
(300AH)
Speed observer selection
IM.SVC IM.VC
0
:
OFF
1
:
ON
Factory default
:
1
Range
:
0~1