Auto-Detect can be configured for Prox Port input format/HID Card Number
Format and External Port Input Format. Please refer to MA SIGMA - Application note -
Wiegand formats for more information. Kindly follow the notes for Auto-Detect.
1.
It is mandatory to configure at least one Wiegand custom slot.
2.
If there are multiple formats defined in the custom slots having same length, then
first matching slot will be considered.
2.
Activate Wiegand Output: This parameter is enabled to allow the Wigand data to be
sent using Wiegand Output Port. If this parameter is disabled then the terminal never
tries to send any data frame through Wiegand port. Configure the Wiegand Output
parameters listed below, for each event which must be communicate through Wiegand
from the terminal:
a.
Select Verification Pass format from available format list, as mentioned under
“Wiegand Format and Associated Values”
b.
Select Verification Fail format from available format list, as mentioned under
“Wiegand Format and Associated Values”
c.
Select Identification Pass format from available format list, as mentioned under
“Wiegand Format and Associated Values”
d.
Select Identification Fail format from available format list, as mentioned under
“Wiegand Format and Associated Values”
e.
Select Duress Finger detection format as ‘None’ or ‘Reverse Wiegand Output’.
When duress finger is detected and verification is successful, terminal will send
Wiegand output in selected form, to access controller. A controller will further
respond by opening door
f.
Select Tamper detection format as ‘None’ or ‘Send 130 bit Wiegand String With
Device Serial Number’. It is a pre-requisite to enable Tamper settings in the
terminal. When tamper event is detected, terminal will send terminal serial
number in a Wiegand string format to access controller, for alerting controller
about the Tamper detection.
g.
Select External Port Output Type as ‘Wiegand Mode’ or ‘Clock & Data mode’. If
you select Clock & Data mode, then respective format will be used for sending
data over Wiegand port.
h.
Set Pulse Width To in terms of microseconds
i.
Set (Pulse) Interval To in terms of microseconds