7. COMMUNICATION DATA LIST
IMR01Y36-E2
56
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
72
(0x0048)
Proportional cycle time
64
R/W 0.1 to 100.0 seconds
M: Relay contact output
V: Voltage pulse output
T: Triac output
D: Open collector output
This item becomes RO (Only reading data
is possible) for the Voltage/Current output
specification.
This parameter is validated when
“0: control output” has been selected at
“ID96: Output assignment.”
M output:
20.0
V, T, D output:
2.0
73
(0x0049)
Unused
⎯
⎯
⎯
⎯
74
(0x004A)
Manual manipulated
output value
♣
64 R/W PID control:
Output limiter low to
Output limiter high
Heat/Cool PID control:
−
Cool-side output limiter (high) to
+
Heat-side output limiter (high)
Position proportioning control:
When there is Feedback resistance
(FBR) input and it does not break:
Output limiter low to
Output limiter high
When there is no Feedback resistance
(FBR) input or the Feedback resistance
(FBR) input is disconnected:
0: Close-side output OFF,
Open-side output OFF
1: Close-side output ON,
Open-side output OFF
2: Close-side output OFF,
Open-side output ON
0.0
75
(0x004B)
Unused
⎯
⎯
⎯
⎯
•
•
•
82
(0x0052)
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Continued on the next page.