7. COMMUNICATION DATA LIST
IMR01Y36-E2
55
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
59
(0x003B)
Heater break alarm (HBA)
set value
64 R/W When CT is CTL-6-P-N:
0.0 to 30.0 A (0.0: Not used)
When CT is CTL-12-S56-10L-N:
0.0 to 100.0 A (0.0: Not used)
If there is no Current transformer (CT) or
CT is assigned to “0: None,” set to RO
(Only reading data is possible).
0.0
60
(0x003C)
Heater break
determination point
64 R/W 0.0 to 100.0 % of HBA set value
(0.0: Heater break determination is
invalidated)
If there is no Current transformer (CT) or
CT is assigned to “0: None,” set to RO
(Only reading data is possible).
If Heater break alarm (HBA) corresponds
to “0: Type A,” set to RO (Only reading
data is possible).
30.0
61
(0x003D)
Heater melting
determination point
64 R/W 0.0 to 100.0 % of HBA set value
(0.0: Heater melting determination is
invalidated)
If there is no Current transformer (CT) or
CT is assigned to “0: None,” set to RO
(Only reading data is possible).
If Heater break alarm (HBA) corresponds
to “0: Type A,” set to RO (Only reading
data is possible).
30.0
62
(0x003E)
Unused
⎯
⎯
⎯
⎯
63
(0x003F)
Unused
⎯
⎯
⎯
⎯
64
(0x0040)
Unused
⎯
⎯
⎯
⎯
65
(0x0041)
PV bias
64
R/W
−
Input span to +Input span
0
66
(0x0042)
PV digital filter
64
R/W 0.0 to 100.0 seconds
(0.0: Unused)
0.0
67
(0x0043)
PV ratio
64
R/W 0.500 to 1.500
1.000
68
(0x0044)
PV low input cut-off
64
R/W 0.00 to 25.00 % of input span
If the Input square root extraction
corresponds to “0: Unused,” set to RO
(Only reading data is possible).
0.00
69
(0x0045)
RS bias *
64
R/W
−
Input span to +Input span
0
70
(0x0046)
RS digital filter *
64
R/W 0.0 to 100.0 seconds
(0.0: Unused)
0.0
71
(0x0047)
RS ratio *
64
R/W 0.001 to 9.999
1.000
* Data on RS bias, RS ratio and RS digital filter is that in Cascade control or Ratio setting.