7. COMMUNICATION DATA LIST
IMR01Y36-E2
72
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
226
(0x00E2)
Controller state 2
31
RO Bit data
Z-TIO module:
Bit 0: Adjustment data error
Bit 1: Data back-up error
Bit 2: A/D conversion error
Bit 3: Unused
Bit 4: Unused
Bit 5: Logic output data error
Bit 6 to Bit 14: Unused
Bit 15: Controller communication error
Z-DIO module:
Bit 0: Unused
Bit 1: Data back-up error
Bit 2 to Bit 14: Unused
Bit 15: Controller communication error
Data 0: OFF
1: ON
[Decimal number: 0 to 32807]
⎯
227
(0x00E3)
Unused
⎯
⎯
⎯
⎯
•
•
•
230
(0x00E6)
231
(0x00E7)
Comprehensive alarm
state
1
1 RO Bit data
Bit 0: Burnout state
Bit 1: Unused
Bit 2: Event 1 state
Bit 3: Event 2 state
Bit 4: Event 3 state
Bit 5: Event 4 state
Bit 6: Heater break alarm (HBA) state
Bit 7 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 127]
⎯
232
(0x00E8)
Controller alarm state
1
2
RO Bit data
Object instance 1:
Bit 0 to Bit 15: Controller 1 to 16
Object instance 2:
Bit 0 to Bit 14: Controller 17 to 31
Data 0: OFF
1: ON
[Decimal number: 0 to 65535]
OR
of Controller state 1 (ID: 225)
⎯
233
(0x00E9)
Error state
1
2
RO Bit data
Object instance 1:
Bit 0 to Bit 15: Controller 1 to 16
Object instance 2:
Bit 0 to Bit 14: Controller 17 to 31
Data 0: OFF
1: ON
[Decimal number: 0 to 65535]
OR
of Controller state 2 (ID: 226)
⎯
1
Validate only when Explicit message communication is used.
Continued on the next page.