7. COMMUNICATION DATA LIST
IMR01Y36-E2
66
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
154
(0x009A)
Derivative action
♣
64
R/W 0: Measured value derivative
1: Deviation derivative
0
155
(0x009B)
Undershoot suppression
factor
♣
64
R/W 0.000 to 1.000
Water cooling:
0.100
Air cooling:
0.250
Cooling gain
linear type:
1.000
156
(0x009C)
Derivative gain
♣
64
R/W 0.1 to 10.0
6.0
157
(0x009D)
ON/OFF action
differential gap (upper)
♣
64 R/W
TC/RTD: 1
V/I: 0.1
158
(0x009E)
ON/OFF action
differential gap (lower)
♣
64 R/W
TC/RTD inputs:
0 (0.0) to Input span (Unit:
°
C [
°
F])
Voltage (V)/Current (I) inputs:
0.0 to 100.0 % of input span
TC/RTD: 1
V/I: 0.1
159
(0x009F)
Action (high) at input error
♣
64 R/W
0
160
(0x00A0)
Action (low) at input error
♣
64 R/W
0: Normal control
1: Manipulated output value at input
error
0
161
(0x00A1)
Manipulated output value
at input error
♣
64 R/W
−
105.0 to +105.0 %
Actual output values become those
restricted by the output limiter.
Position proportioning control:
If there is no Feedback resistance (FBR)
input or the Feedback resistance (FBR)
input is disconnected, an action taken
when abnormal is in accordance with
the value action setting during STOP.
0.0
162
(0x00A2)
Manipulated output value
at STOP mode [heat-side]
♣
64 R/W
−
5.0
163
(0x00A3)
Manipulated output value
at STOP mode [cool-side]
♣
64 R/W
−
5.0 to +105.0 %
Position proportioning control:
Only when there is Feedback resistance
(FBR) input and it does not break, the
Manipulated output value [heat-side] at
STOP is output.
−
5.0
164
(0x00A4)
Output change rate limiter
(up) [heat-side]
♣
64 R/W
0.0
165
(0x00A5)
Output change rate limiter
(down) [heat-side]
♣
64 R/W
0.0 to 100.0 %/seconds
(0.0: OFF)
Becomes invalidated when in Position
proportioning control.
0.0
166
(0x00A6)
Output limiter high
[heat-side]
♣
64 R/W Output limiter low [heat-side] to 105.0 %
Position proportioning control:
Becomes validated only when there is
Feedback resistance (FBR) input and it
does not break.
105.0
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Continued on the next page.