IMR01Y36-E2
47
7. COMMUNICATION DATA LIST
7.1 Reference to Communication Data List
Attribute contents of the controller object are described to the communication data list.
The controller objects consist of the three types below.
•
Z-TIO module object (0x64: 64Hex)
•
Z-TIO module extended object (0x65: 65Hex)
•
Z-DIO module object (0x66: 66Hex)
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
1
(0x0001)
Measured value (PV)
64
RO Input scale low to Input scale high
⎯
2
(0x0002)
Current transformer (CT)
input value monitor
64 RO CTL-6-P-N:
0.0 to 30.0 A
CTL-12-S56-10L-N: 0.0 to 100.0 A
⎯
3
(0x0003)
Unused
⎯
⎯
⎯
⎯
(1) ID:
Attribute ID
Attribute ID is written using both of decimal and hexadecimal (in
parentheses)
numbers.
(2) Name:
The communication item name is written.
(3) Number of data items:
The number of data items is written.
1: Only object instance 1 is validated
2: Only object instance 1 and 2 are validated
16: Validate for object instance 1 to 16
31: Validate for object instance 1 to 31
64: Validate for object instance 1 to 64
128: Validate for object instance 1 to 128
With respect to the following communication data of the Z-TIO module,
the data of the indicated channels are “0”.
•
Two-channel type module:
Data of the 3rd and 4th channels
•
Heat/cool control and position proportioning control:
Data of the 2nd and 4th channels *
•
Cool-only communication data of heat/cool control:
Data of the 2nd and 4th channels *
* Communication data with a
♣
mark in the name column
(1) (2)
(3)
(4)
(5)
(6)