7. COMMUNICATION DATA LIST
IMR01Y36-E2
74
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
242
(0x00F2)
RUN/STOP logic
selection
1, 2
1 R/W 0: RUN
=
0, STOP
=
1
1: RUN
=
1, STOP
=
0
Validate to RUN/STOP (ID: 234) and the
4th word and the 5th word in the Polling
I/O communication setting item (OUT).
However, invalidate to the RUN/STOP
transfer (ID: 36) and the ID6 of Z-DIO
module object (0x66: 66Hex).
0
243
(0x00F3)
Setting validity selection
1
1 R/W 0: The setting is validated when the
power is turned off once after the
setting is changed and it is turned on
again.
1: The setting is validated just after the
setting is changed.
Object data
•
The data of “Controller
communication item setting object
(0xC7)”
•
The data of “Number of Polling I/O
communication controllers (ID: 236)”
0
244
(0x00F4)
Unused
⎯
⎯
⎯
⎯
245
(0x00F5)
Controller address
setting
1, 2
1
R/W 0 to 32 (0: No communication)
1 to 31
246
(0x00F6)
Action mode selection
1, 2,
♦
1 R/W Bit data
Bit
0: Address setting method transfer
0: Continuous setting
1: Free setting
Bit
1: PID/AT transfer Polling I/O
communication
0:
Invalidate
1:
Validate
Bit
2 to
Bit
15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 3]
1
247
(0x00F7)
Automatic acquisition of
controller address
1, 2
1
R/W 0: Do not execute the automatic acquisition
1: Execute the automatic acquisition
0
248
(0x00F8)
Unused
⎯
⎯
⎯
⎯
•
•
•
255
(0x00FF)
1
Validate only when Explicit message communication is used.
2
The setting is validated when the power is turned off once after the setting is changed and it is turned on again.
: It is possible to set in the communication environment setting by the rotary switch of COM-JH (Refer
to P. 23) or configuration tool (Refer to P. 33).
♦
Communication environment setting by rotary switch of COM-JH is possible.