6. DeviceNet COMMUNICATION
IMR01Y36-E2
46
Data setting by Explicit message communication
Corresponding object: Controller object: Z-TIO module object (0x64: 64Hex)
Z-TIO module extended object (0x65: 65Hex)
Z-DIO module object (0x66: 66Hex)
Object class ID: 64, 65, 66
Instance ID:
1 to 64 (Z-TIO module)
1 to 128 (Z-DIO module)
Attribute ID:
1 to 255
[Example] Node address of COM-JH: 1
When set in “100” in set value (SV) of CH3 of Z-TIO module 1
Node address (MAC ID)
1
Service code
10H (Set_Attribute_Single)
Object class ID
64
Instance ID
3 (CH3 of Z-TIO module 1)
Attribute ID
45 (Set value (SV))
Write data
100
When set in “50” in proportional band [heat-side] of CH2 of Z-TIO module 2
Node address (MAC ID)
1
Service code
10H (Set_Attribute_Single)
Object class ID
64
Instance ID
6 (CH2 of Z-TIO module 2)
Attribute ID
46 (Proportional band [heat-side)
Write data
50
When set in “Unused” in operation mode of CH4 of Z-TIO module 1
Node address (MAC ID)
1
Service code
10H (Set_Attribute_Single)
Object class ID
65
Instance ID
4 (CH4 of Z-TIO module 1)
Attribute ID
1022 (Operation mode)
Write data
0 (Unused)
When set in “ON” in DO1 manual output of Z-DIO module 1
Node address (MAC ID)
1
Service code
10H (Set_Attribute_Single)
Object class ID
66
Instance ID
1 (Z-DIO module 1)
Attribute ID
2007 (DO manual output)
Write data
1
Z-TIO module
extended object
Attribute ID
+
1000
Z-DIO module object
Attribute ID
+
2000