7. COMMUNICATION DATA LIST
IMR01Y36-E2
68
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
179
(0x00B3)
Proportional band adjusting
factor [heat-side]
♣
64
R/W 0.01 to 10.00 times
1.00
180
(0x00B4)
Integral time adjusting
factor [heat-side]
♣
64
R/W 0.01 to 10.00 times
1.00
181
(0x00B5)
Derivative time adjusting
factor [heat-side]
♣
64
R/W 0.01 to 10.00 times
1.00
182
(0x00B6)
Proportional band adjusting
factor [cool-side]
♣
64
R/W 0.01 to 10.00 times
1.00
183
(0x00B7)
Integral time adjusting
factor [cool-side]
♣
64
R/W 0.01 to 10.00 times
1.00
184
(0x00B8)
Derivative time adjusting
factor [cool-side]
♣
64
R/W 0.01 to 10.00 times
1.00
185
(0x00B9)
Proportional band limiter
(high) [heat-side]
♣
64 R/W
TC/RTD:
Input span
V/I: 1000.0
186
(0x00BA)
Proportional band limiter
(low) [heat-side]
♣
64 R/W
TC/RTD inputs:
0 (0.0) to Input span (Unit:
°
C [
°
F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of input span
0 (0.0): ON/OFF action
(ON/OFF action for both heat and cool
actions in case of a Heat/Cool PID control
type.)
TC/RTD:
0 (0.0)
V/I: 0.0
187
(0x00BB)
Integral time limiter (high)
[heat-side]
♣
64 R/W
3600
188
(0x00BC)
Integral time limiter (low)
[heat-side]
♣
64 R/W
PID control or Heat/Cool PID control:
0 to 3600 seconds or
0.0 to 1999.9 seconds
Position proportioning control:
1 to 3600 seconds or
0.1 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
PID control,
Heat/Cool PID
control: 0
Position
proportioning
control: 1
189
(0x00BD)
Derivative time limiter
(high) [heat-side]
♣
64 R/W
3600
190
(0x00BE)
Derivative time limiter
(low) [heat-side]
♣
64 R/W
0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
0
191
(0x00BF)
Proportional band limiter
(high) [cool-side]
♣
64 R/W
TC/RTD:
Input span
V/I: 1000.0
192
(0x00C0)
Proportional band limiter
(low) [cool-side]
♣
64 R/W
TC/RTD inputs:
1 to input span or 0.1 to input span
(Unit:
°
C [
°
F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of input span
TC/RTD:
1 (0.1)
V/I: 0.1 %
♣
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Continued on the next page.