6. DeviceNet COMMUNICATION
IMR01Y36-E2
36
Conduct parameter set according to the procedure described below.
1.
Set measured data items (IN) with a parameter setting screen of COM-JH.
•
Set attribute ID “1” of Measured value (PV) in “IN ch1 (Parameter 1).”
•
Set attribute ID “14” of Manipulated output value (MV1) monitor in “IN ch2 (Parameter 2).”
•
“0” is set to unused IN ch (Parameter 3 to 32).
In addition to Alarm state and RUN/STOP state assigned as fixed, up to 32 types of
measured data items can be selected.
Set measured data items in order starting from IN ch1 (Parameter 1). If any of the
following values is set, all items from that item to IN ch32 (Parameter 32) are the same as
those when set at “0.”
•
If at “0”
•
If set to attribute ID to which no communication data items are assigned
•
If at 231 to 236 or 238 to 243 as attribute ID
When setting the communication items of a Z-TIO module extended object (0x65: 65Hex)
or Z-DIO module object (0x66: 66Hex), set the attribute ID number with the appropriate
offset value (1000 or 2000) added.
•
0x65: 65Hex: Attribute ID + 1000
•
0x66: 66Hex: Attribute ID + 2000
For attribute ID of the communication items, refer to
7. COMMUNICATION DATA
LIST (P. 47)
.
Continued on the next page.
Parameter Value
1 IN
ch1
1
2 IN
ch2
14
3 IN
ch3
0
4 IN
ch4
0
32 IN
ch32
0
Attribute ID of Measured value (PV): 1
Attribute ID of Manipulated output value
(MV1) monitor: 14
Set “0” in unused items